CC28 Transmitter

For flammable gases and vapors in Ex zones


If combustible gases and vapors are to be monitored in Ex zones, the CC28 transmitter is a reliable and economical solution. The CC28 uses an analog (4-20 mA) signal to provide measured values and status information. The special stack effect ensures shortest response times of a few seconds for a fast warning of explosion hazards. In combination with GfG's proven controllers, installation in new gas detection systems as well as retrofitting in existing systems is possible.

The CC28 uses catalytic combustion (CC) to detect combustible gases and vapors such as methane, propane and hydrogen. The long-life sensors make the CC28 an economical solution for detecting a wide range of combustible gases in the measurement ranges 0 to 100% LEL and 0 to 4% by volume (NH3). Automatic temperature compensation and linearization of the measurement signals ensure high measurement accuracy.

Explosion protection, functional safety and device protection
The CC28 has ATEX certification for use in Ex Zone 1, and its hardware complies with the European Functional Safety Standard DIN EN 61508-2: 2011 (SIL). The housing is protected against dust and water ingress (protection class: IP64). An optional weatherproof housing provides additional protection.

Communication and service
Signal transmission is done via the analog industry standard (4-20 mA). Operating states are indicated by the transmitter via two status LEDs. Service and adjustments are carried out on site using the optional RC2 remote control (one-man adjustment). The pre-adjusted sensors can be easily replaced thanks to Smart Sensor technology. Test gases can be supplied for function tests using a flow adapter.

Key features at a glance:


General information:

  • Measurement method: Catalytic combustion (CC)
  • for combustible gases and vapors
  • short response time due to stack effect
  • expected sensor lifetime: 5 years
  • signal transmission: 4-20 mA
  • protection class: IP64

Approvals / Certifications:

  • ATEX certification: II 2G Ex demb [ib] IIC T4 Gb
  • SIL 2/3 (hardware)

Optionally available:

  • operating unit RC2, windshield, weatherproof housing, flow-through adapter

Detectable gases

LEL combustible gases
C2H2 Acetylene
C2H4 Ethylene
C2H6O Ethanol
C2H6 Ethane
C2H6O Dimethyl ether
C3H4 Propine
C3H6 Propene
C3H6O Acetone
C3H6O2 Methyl acetate
C3H8 Propane
C3H8O n-Propanol
C4H8O 2-Butanon (MEK)
C4H8O2 Ethyl acetate
C4H10 n-Butane
C4H10O n-Butanol
C5H12 Pentane (n)
C6H6 Benzene
C6H12 Cyclohexane
C6H12O Methyl isobutyl ketone (MIBK)
C6H14 n-Hexane
C7H8 Toluene
C7H16 n-Heptane
C8H18 Octane (n)
C9H20 n-Nonane
CH4 Methane
CH4O Methanol
CO Carbon monoxide
H2 Hydrogen
NH3 Ammonia
Other gases on request.

Downloads

Extensions and accessories

Remote calibration adapter

Remote calibration adapter


To facilitate the regular function check of transmitters
» more

Weatherproof housing

Weatherproof housing


Weatherproof housing for various transmitters
» more

Test gases

Test gases


You can find an overview of our test gases here
» more

Accessories CC28

Accessories CC28


Here you'll find the complete list of accessories for the CC28
» download PDF

Our experts look forward to answer your questions! How to find us