Question:

I work at a fire department. We recently ran into a problem in the area where we charge lead acid batteries that we use in our engines and boats. One of the batteries became overheated while being recharged. What gases or hazardous atmospheric conditions are associated with lead acid battery charging stations? Can batteries release flammable gas? If the batteries contain sulfuric acid, does that mean they can produce and release toxic H2S? We thought we smelled something. What should we measure?

Answer:

Thanks for your very good question.

Lead acid batteries are used to power forklifts, carts and many other types of machinery in many industrial settings.  Many facilities have charging areas where multiple heavy duty lead acid batteries are recharged at the same time.  In some cases facilities maintain large banks of lead acid batteries that are used to provide backup power to critical systems during an emergency.  Fire engines, HAZMAT and emergency response vehicles frequently include banks of lead acid batteries for the same purpose.  Gases produced or released by the batteries while they are being charged can be a significant safety concern, especially when the batteries are located or charged in an enclosed or poorly ventilated area, or on the truck.

Sulfuric acid contains sulfur, and hydrogen sulfide (H2S) is a possible by-product of over-charging and battery decomposition. If you smell the rotten egg odor of H2S in the charging area, you should assume that this very dangerous gas is a possibility.  You should leave the area, and use a gas detecting instrument with an H2S sensor to confirm whether the gas is present before returning.

However, H2S is not the most common gas associated with charging or discharging lead acid batteries that contain sulfuric acid.  Given the over-heating and other problems you mentioned, you may not find H2S, but you probably will find the presence of other atmospheric hazards when you test the atmosphere in the area with your gas detector.

The most common reaction byproducts associated with sulfuric acid (H2SO4) are hydrogen and sulfur dioxide.  Overcharging, or lead acid battery malfunctions can produce hydrogen.  In fact, if you look, there is almost always at least a little H2 around in areas where lead batteries are being charged.

Overcharging, especially if the battery is old, heavily corroded or damaged can produce H2S. Deteriorated, old or damaged lead acid batteries should be removed from service, as damaged batteries are much more likely to be associated with production of H2S.

Sulfuric acid reacts with a number of metals and substances to produce SO2 as well as other “sulfur oxides” (SOx) such as SO3, SO4, S2O, etc.  Many sulfur oxides have a pungent odor, but they are NOT H2S.  H2S is a reduced sulfide, not an oxide.  When you have a spill, SO2 is generally the most common gaseous sulfur reaction by-product.

During discharge of a lead acid battery you have the following two half-cell reactions.  Neither SO2 or H2S are normally produced, even by catastrophic discharge!

Negative plate reaction:

Pb (solid) + HSO4 (aqueous) → PbSO4 (solid) + H+ (aqueous) + 2e

Positive plate reaction:

PbO2 (solid) + HSO4 (aqueous) + 3H+ (aqueous) + 2e → PbSO4 (solid) + 2H2O

The total reaction can be written as:

Pb (solid) + PbO2 (solid) + 2H2SO4 (aqueous) → 2PbSO4 (solid) + 2H2O

During charging, (especially in the event of overcharging), lead acid batteries produce oxygen and hydrogen.  These gases are produced by the electrolysis of water from the aqueous solution of sulfuric acid.  Since the water is lost, the electrolyte can be depleted.  This is why you need to add water to “wet” (flooded type) non-sealed lead acid batteries.  When a lead acid battery cell “blows” or becomes incapable of being charged properly, the amount of hydrogen produced can increase catastrophically:

Water is oxidized at the negative anode:  2 H2O (liquid) → O(gas) + 4 H(aqueous) + 4e

The protons (H+) produced at the anode are reduced at the positive cathode:  2 H+ (aqueous) + 2e → H2

So, in an area where lead acid batteries are being charged, the first gas to measure is H2.

Hydrogen is not toxic, but at high concentrations is a highly explosive gas. The 100% LEL concentration for hydrogen is 4.0% by volume.  At this concentration, all it takes is a source of ignition to cause an explosion.  Sparking from a battery terminal as it is connected or disconnected from the charging system is more than adequate as a source of ignition energy.  That’s why lead acid batteries should only be charged in well ventilated areas.

The best way to measure hydrogen in an area where you are charging batteries is with a permanently installed monitoring system.  You can use a standard catalytic LEL sensor, or you can measure the hydrogen by means of a substance specific electrochemical sensor.  The sensor and housing need to be designed and certified for installation and use in hazardous locations characterized by the potential presence of combustible gas.  Since hydrogen is lighter than air, H2 sensors are usually mounted to the wall or ceiling at a height at least slightly above the source of gas.

Readings from the H2 sensors can displayed right where the sensor is located, or on a remotely located controller or monitor.   Readings from the sensors can be used to activate relays, fans or alarms, or the information can be transmitted and integrated into the facility’s overall environmental health and safety and fire detection systems.

For LEL range measurement, using a standard catalytic combustible gas (CC) sensor with a range of 0 – 100% LEL is a good approach.  For situations where you need to take action at a lower concentration, using an electrochemical (EC) toxic gas sensor to measure the hydrogen may be a better approach.  The typical range for an EC hydrogen sensor is 0 – 2,000 ppm.  (This is equivalent to a range of 0 – 5.0% LEL.)

In the event of a sulfuric acid spill, or where the sulfuric acid is coming into contact with metals and / or other materials, you may need to measure SO2 as well.  Although this is normally not necessary in charging areas where the acid is fully contained in the batteries.

If you are concerned with aerosol droplets of sulfuric acid, you can directly measure H2SO4 as well.  Once again, this is not normally a concern in battery charging areas.

Deteriorated, old or damaged lead acid batteries should be removed from service, as damaged batteries are much more likely to be associated with leakage leading to the production of SO2, or charging malfunction which could lead to the production of H2S

I hope this info is helpful!

Do you have another question? Simply ask Bob! Contact us